class: middle, center, title-slide count: false
Lecture 9: Transient Stability
Antonin Colot
[email protected]
- Classification power system stability (Reminder)
- Principle of transient stability
- Swing equation
- Practical Example
- Dynamic Security Assessment
- Nowadays
- Proposed definition:
Power system stability is the ability of an electric power system, for a given initial operating condition, to regain a state of operating equilibrium after being subjected to a physical disturbance, with most system variables bounded so that practically the entire system remains intact. [2]
.footnote[[1] Hatziargyriou, Nikos, et al. "Definition and classification of power system stability–revisited & extended." IEEE Transactions on Power Systems 36.4 (2020): 3271-3281.]
- Consider a generator bus connected through a transformer to a infinite bus system (
$\bar{V}_B = V_B$ is an ideal voltage source). - The mechanical power delivered through the shaft is
$P_m$ . - The electrical power delivered to the grid is denoted
$P_e$ . - In steady-state, the synchronous machine is modelled as a constant voltage source
$E'\ e^{j\delta}$ behind its transient reactance$X'_d$ . - Finally,
$X_{tr}$ is the leackage reactance of the transformer.
Consider a simple radial system.
Assuming no transmission-line losses:
If we define
The electrical power
At equilibrium,
When we increase
There exist TWO equilibrium points for
Question: What happens if
In synchronous machines, the rotor rotates at the same angular speed as the magnetic field produced by the stator. If we denote
The field produced by the rotor and the stator tend to align. If they are not aligned, an electromechanical torque is produced. This misalignment is represented by the electrical angle. A greater angle induces a larger torque. BUT if the angle is too large, the machine loses synchronism and the torque becomes 0.
.footnote[[2] Lectures given by Prof. Thierry Van Cutsem https://thierryvancutsem.github.io/home/courses.html]
Consider this equation:
with
Let us consider the following sequence of actions:
- Pre-fault conditions; the impedance between generators and the infinite bus system is
$j 0.5$ pu. - During-fault conditions; one line is short-circuited, the impedance becomes
$j 3$ pu. - Post-fault conditions; the short-circuit is cleared by disconnecting a line, the impedance becomes
$j 1$ pu.
For the system to be stable, the system has to stabilize at
We will now look at how the system moves from the equilibrium point $\delta_1$ to equilibrium point $\delta_2$
Let us define the following quantities;
Multiplying both sides by
We then define
where
One can write the swing equation by substituing
Finally, we make the reasonable assumption that
.footnote[[3] Mohan, N. (2012). Electric power systems: a first course. John Wiley & Sons.]
What can we say about the swing equation?
- If the mechanical power provided at the shaft
$P_m$ is greater than the electrical power transferred to the network$P_e$ , the machine accelerates$\frac{d^2\delta}{dt^2} = \frac{d\Delta\omega}{dt} > 0$ , where$\Delta\omega$ is the deviation from the synchronous speed$\omega_{syn}$ . - It decelerates if the electrical power is greater than the mechanical power.
- The acceleration is proportional to the machine inertia
$H$ = time it takes for the machine to reach its nominal speed if the mechanical power provided at the shaft is$S_{system}$ .
What is the inertia of PV panels?
Swing equation:
Rearranging the terms and multiplying both sides by
Applying change of variables
Assume
The left term
As long as
Let us consider the following system; at time
For a stable system, we highlighted that:
For our little example, one can write the same condition:
During the first part (Area A), the machine accelerates. After the fault (Area B), the machine decelerates and the net acceleration becomes 0. At angle
Without any damping (kinetic energy losses), the system oscillates indefinitely between angle
However, in a real system, the damping would cause the machine to settle down at an angle
Synchronous machines have damper windings . In perfect steady state, the magnetic fields produced by both the stator and the rotor are fixed relative to the rotor so there is no current in the dampers. On the other hand, if the rotor moves with respect to the magnetic field, the current induced in the dampers create a damping torque according to Lenz's law.
Let us come back to our definition of stability for our little system:
What are the conditions to ensure there exists $\delta_{cl}$ such that Area A = Area B?
We introduce the concept of critical clearing angle
Visual representation
Mathematical formulation
One has to determine the angle
Let us consider the following system:
and the following data:
We can derive the following equivalent:
where
The power transfer from the machine to the infinite-bus system takes the following form:
- Current from
$\bar{E}_{t}$ to$\bar{E}_{B}$ $$\bar{I}_{t\rightarrow B} = \frac{\bar{E}_{t}-\bar{E}_{B}}{jX_{T} - jX_{d}'}$$ -
$\bar{I}_{t\rightarrow B}$ is the same as the one from$\bar{E'}$ to$\bar{E}_{t}$ $$\bar{E}' = j X_{d}' \bar{I}_{t\rightarrow B} + \bar{E}_{t} = 1.05095 e^{j 38.2057/180}$$ - Find
$P_e$ $$P_e = \frac{1.05095\ 1\ \sin(38.2057/180)}{1.3} = 0.5$$ - Initially, the system is at equilibrium.
$$P_m = P_e = 0.5$$
In the following, we will compute the maximum power outputs for three different conditions: Pre-fault, During-Fault and Post-Fault. It will allow us to determine the 3 different
We compute the maximum power output while assuming $E'$ does not change.
If the transient stability study lasts a second or less, it is reasonable to consider, as a first-order approximation, that the exciter of the synchronous machine cannot respond in such short amount of time. Hence, $E'$ does not change
Maximum power output:
A short-circuit occurs between lines
We can derive the following Thevenin's equivalent
where
and then get the maximum power output:
The line
The impedance of the path connecting the machine to the infinite-bus system becomes
The maximum power output is:
The final
with
Area A
$$
\begin{aligned}
\int_{\delta_{0}}^{\delta_{cct}} \left(P_{m,pu}-P_{e,fault,pu}\right) d\theta &= P_{m,pu} \left(\delta_{cct} - \delta_{0}\right) - \int_{\delta_{0}}^{\delta_{cct}} \hat{P}_{e,df} \sin \theta d\theta \
&=P_{m,pu} \left(\delta_{cct} - \delta_{0}\right) + \hat{P}_{e,df} \left(\cos \delta_{cct} -\cos \delta_{0}\right) \\
\end{aligned}
$$
Area B
$$
\begin{aligned}
\int_{\delta_{cct}}^{\delta_{max}} \left(P_{e,pf,pu}-P_{m,pu}\right) d\theta &= P_{m,pu} \left(\delta_{cct} - \delta_{max}\right) - \int_{\delta_{cct}}^{\delta_{max}} \hat{P}_{e,pf} \sin \theta d\theta \
&=P_{m,pu} \left(\delta_{cct} - \delta_{max}\right) + \hat{P}_{e,pf} \left(\cos \delta_{cct} -\cos \delta_{max}\right) \\
\end{aligned}
$$
Equal-area criterion
We can find out the critical clearing angle.
The purple star corresponds to
In order to find the critical clearing time, one would need to solve the swing equation:
where
Thus, let us assume that the acceleration
- We pick the maximum acceleration for angles in
$[\delta_1,\delta_{cct}]$ . - We pick the minimum acceleration for angles in
$[\delta_1,\delta_{cct}]$ .
From the following figure
it is clear that the acceleration is maximum for
We have:
With $H = 4.5$s, we can derive a lower and an upper bound for the critical clearing time
If the actual clearing time is denoted
- If
$t^*>CCT_{max}$ , the system is unsafe! - If
$t^*<CCT_{min}$ , the system is safe! - If
$CCT_{min}<t^*<CCT_{max}$ , we have no guarantee if the system is safe or not.
Swing equations with damping coefficient
Euler discretization
Results without damping ($t_{cl} = 0.214 s \leq CCT$)
The fault is cleared after 214 ms (lower bound on the clearing time). As expected from previous calculations, the system is safe.
Results with damping ($t_{cl} = 0.214 \leq CCTs$)
The fault is cleared after 214 ms (lower bound on the clearing time). As expected from previous calculations, the system is safe. The damping adds energy dissipation, which allows the system to stabilize around
Results without damping ($t_{cl} = 0.239 s \geq CCT$)
The fault is cleared after 239 ms (upper bound on the clearing time). The machine loses synchronism.
Results with damping ($t_{cl} = 0.239 s \geq CCT$)
The fault is cleared after 239 ms (upper bound on the clearing time). The system is stable thanks to the damping effect (energy dissipation).
- Based on fast time domain contingency simulations.
- Study main stability issues such that: Voltage, Transient and Small-Signal (not covered throughout this course).
- Start from actual and future operating points.
- Has to be visual for the operators
$\rightarrow$ show the type of instability, where it comes from and even possible solutions.
Main question that DSA should answer:
Imagine a set of major, yet credible contingencies, can the system resist such events without jeopardizing its integrity?
If yes, then the states are determined secure
There are basically two types of analysis: off-line and on-line.
Off-line analysis
-
They are subjected to forecast errors
$\rightarrow$ system security cannot be taken for granted. -
But they can be performed with no constraints on time (performed day-ahead in order to set up a recommended operating schedule)
On-line analysis
-
Not prone to forecast errors since they are based on real-time information.
-
But need to be fast.
.footnote[[4] Kerin, U., Balaurescu, R., Lazar, F., Krebs, R., & Balasiu, F. (2012, July). Dynamic security assessment in system operation and planning—First experiences. In 2012 IEEE Power and Energy Society General Meeting (pp. 1-6). IEEE.]
- Mainly static analyses.
- Goal is to ensure a sufficient load power margin.
- List of contingencies: all single-component outages.
.footnote[[5] Lecture of last year presented by Prof. Louis Wehenkel https://bcornelusse.github.io/ELEC0447-analysis-power-systems/?p=lecture9.md#20]
- We want to avoid that:
- Simulations with different three-phase short-circuits at various locations.
- And with different clearing schemes!
- Very time consuming computations.
- Integration of large off-shore wind parks, and PV systems without reinforcing the network.
- Large power plants are decommissioned, and conventional generators are no longer accepted in urban areas.
- New units are built far away from load centers.
- Hard to build new lines because of public debates and environmental constraints.
This leads to a weaker electrical system, more prone to stability issues.
There's a need for tools that can quickly perform security assessment to guarantee a secure system.
- For static analyses, we rely on power flow solvers to estimate the state of the system.
- With increasing penetration of RES, probabilistic approaches are envisioned to perform risk assessment.
- But traditional power flow solvers based on Newton-Raphson methods are too slow.
- Usage of AI tools to derive approximate solutions of the power flow equations.
Donon, B., Clément, R., Donnot, B., Marot, A., Guyon, I., & Schoenauer, M. (2020). Neural networks for power flow: Graph neural solver. Electric Power Systems Research, 189, 106547.
-
For dynamic analyses, we study the time-evolution of a power system trajectory (e.g. internal angle in transient stability)
-
It requires solving the differential-algebraic equations for multiple scenarios (different short-circuit locations, different clearing schemes).
-
Usage of reachability analysis techniques: gives the reach set, i.e., the set that contains all possible system trajectories.
Chen, Y. C., & Dominguez-Garcia, A. D. (2012). A method to study the effect of renewable resource variability on power system dynamics. IEEE Transactions on Power Systems, 27(4), 1978-1989.
class: end-slide, center count: false
The end.